Permit Number: T12CM02304
Parcel: 113080240

Address:
2904 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM02304
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2012 TERRY STEVENS ZONING REVIEW Denied DEVELOPMENT PACKAGE REQUIRED
04/30/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/30/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/30/2012 ROBERT SHERRY WATER REVIEW Approved
04/30/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; CODE REVIEW (OCCUPANT LOADS): THE RETAIL SALES OCCUPANCY IS DETERMINED USING 100 SF/PERSON. REVISE PER THE IBC TABLE 1004.1.1.
2. SHEET TS1; CODE REVIEW (EXITING): THE CORRIDOR PROTECTION IS LISTED AS "NOT REQUIRED". IS THERE NO EXISTING CORRIDOR? VERIFY.
3. SHEET A1.0; FLOOR PLAN: A SECTION 4/A3.0 IS SHOWN ON THE PLAN, BUT THERE IS NO SECTION 4 ON SHEET A3.0. REVISE.
4. SHEET A3.0; SECTION 3: A DETAIL 7/S2.1 IS INDICATED ON THE SECTION, BUT THERE IS NO DETAIL 7 ON SHEET S2.1. REVISE.
5. SHEET A3.0; SECTION 1: THE DETAIL 3/S2.1 INDICATED ON THE SECTION IS NOT CORRECT. REVISE.
6. SHEET A3.0; SECTION 2: THE DETAIL 4/S2.1 INDICATED ON THE SECTION IS NOT CORRECT. REVISE.
7. SHEET S2.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 5): THE CALCULATIONS INDICATE BEAM B-1 IS A 5 1/8" X 19 1/2" GLB, WHILE THE PLAN INDICATES A 5 1/8" X 18" GLB. CLARIFY.
8. SHEET S1.1; DETAIL 1: INDICATE 4 ANCHOR BOLTS ON THE LOWER BASE PLATE.
9. SHEET S1.1; DETAIL 3: CUT THIS DETAIL ON THE PLAN.
10. SHEET S1.1; DETAILS 2 AND 3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
11. SHEET S2.1; SECTIONS 1, 2, 3, 5, AND 6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
12. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/30/2012 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
04/30/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/30/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/30/2012 ERIC NEWCOMB ADA REVIEW Passed
05/01/2012 KEN BROUILLETTE FIRE REVIEW Approved
05/09/2012 CPIERCE1 ENGINEERING REVIEW Needs Review