Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM02222
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/21/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; detail 5/A6.0 states that the actual scupper width will be shown in the rainfall calculations on sheet A3 which doesn't exist. [Original comment: Provide the dimensions for the roof drainage scuppers and downspouts (see detail 6/A6.0). Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006, and Section 1611.1, IBC 2006.] |
| 05/21/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. |
| 05/23/2012 | DAVID RIVERA | ZONING | REVIEW | Passed |