Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM02138
Parcel: 107141450

Address:
2537 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM02138
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a waste and vent isometric for the new work associated with the installation of the clothes washer and the urinal. Reference: Section 103.2.3, UPC 2006.
2. Appliances (e.g. coffee, tea, espresso, and ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. the clothes washer). Reference: Section 609.10, UPC 2006.
4. Coordinate the waste and gas plan with the waste isometric (e.g. the connection point for the waste pipe from the hand sink, P5, in the island with the building drain) and clarify where the upper terminal cleanout for the 4" building drain will be located. Reference: Sections 103.2.3, 707.5, and 707.11, UPC 2006.
5. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
6. Provide a vent for each fixture trap (e.g. the floor sink, P7, in the service aisle). Reference: Sections 901.0 and 910.1, UPC 2006.
7. Provide the specifications for the gravity grease interceptor and show that the size of the interceptor complies with Section 1014.3.6, UPC 2006.
8. Provide an automatic fuel shutoff valve for the gas-fired appliances located under the type I hood. Reference: Section 904.11.2, IFC 2006.
05/22/2012 ROBERT SHERRY WATER REVIEW Approved
05/23/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a design for the proposed Type I hood installation that clearly shows that the installation will comply with the requirements of Sections 302, 506, 507, and 508, IMC 2006. Reference: Section 106.3.1, IMC 2006.
2. Provide the listing information for the proposed tandoor oven. Reference: Section 301.4, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2012 GERARDO BONILLA OUT TO CUSTOMER Completed