Permit Number: T12CM02128
Parcel: 140280380

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM02128
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2012 LOREN MAKUS ENGINEERING REVIEW Approved
04/24/2012 CARL SCHULTZ FIRE REVIEW Approved
04/25/2012 ERIC NEWCOMB ADA REVIEW Passed
04/25/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/25/2012 STEVE SHIELDS ZONING REVIEW Approved
04/25/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
04/26/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Replot sheet P1 so that the background floor plan is visible. Reference: Section 106.3.1, IPC 2006.
2. Show where the relief valve of the reduced pressure backflow preventer will discharge without causing damage. Reference: sections 608.14 and 608.16.10, IPC 2006.
04/26/2012 ROBERT SHERRY WATER REVIEW Approved
04/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/03/2012 FRODRIG2 WWM REVIEW Needs Review