Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Comments:
1. TEP SR Book indicates Fault at TEP transformer to be 52,400aic. Provide Fault current calculations and show how the fault levels will be brought down to safe levels at the 1,000 amp and 1,200 amp disconnects.
2. The new 3,000 amp service will require a new system Ground, please remove "use existing system.

RT Majuta
Elect Pln Review
PDSD, C of Tuc
4/18/12