Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01988
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2012 | CARL SCHULTZ | FIRE | REVIEW | Denied | Please indicate means of egress illumination for market and patio (illumination emergency power) per IFC & IBC 1006 |
| 05/04/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Detail 1/A0 is not 1/4" scale. It really is not to any standard scale. Please redraw to an acceptable standard scale and resubmit. 2. Please provide an EXIT plan showing exit width calculations and number of required exits as required by Section 1019. 3. At detail 8/A4, please specify the testing lab 2 hour assembly number equivalent for this detail. 4. At detail 3/A4, please show the finished grade of the other side of the stem wall and elevation difference from the patio surface. 5. Please show detail 3/A4 on detail 2/A2. 6. At detail 4/A3, please define what the "PLATE" opening infill material is and how it is fastened to the steel frame. 7. Please provide new addition roof plans and show all slopes, drainage, crickets, gutters and downspouts. 8. Detail 1/A1: a. Note 10 is incorrect for the downspout at detail 1/A1. It should be 12. b. Where is the gutter and down spout for the metal roof? 9. Please show all gutters and down spouts on details 1, 2 and 4/A2. 10. At detail 4/A5, please include gutter detail and roof flashing. 11. Sheet E43: a. Please show all exit signs both new and existing for exit egress; i.e. patio exit into building exit out front entrance. b. Please coordinate exit signs with detail 1/A1 12. Detail 1/A1: The new ramp added to the front entrance is not compliant with the 2006 IBC, Sections 1105.1 and 1008.1.4 and ICC ANSI 117.1, Sections 404. Please rework and resubmit. 13. At details 1/A1, 3/A4 and 5/A5, notes refer to the finished grade of the patio to be constructed at 1" below the finished elevation floor of the existing market. This will not help accessibility of the new entrance from the patio as it does not comply with ICC ANSI 117.1, Section 303 for a maximum 1/4" high floor change. Please clarify and resubmit. END OF REVIEW |
| 05/07/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/09/2012 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/09/2012 | LHANLY1 | WWM | REVIEW | Passed | |
| 05/09/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/09/2012 | LHANLY1 | WATER | REVIEW | Passed | |
| 05/09/2012 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Passed |