Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM01914
Parcel: 11205283E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01914
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. There are several sheets that are not compliant with the City of Tucson minimum lettering size of 3/32" both upper and lower case. Please revise all sheets to meet these minimal standards and resubmit.
2. Please provide a new address for the work to be completed in the east side adjacent. A new permit will have to be issued for this work.
3. Please provide structural calculations and details for:
a. The wall mounted water heater. Include analysis of the wall that the water heater is to be supported.
b. All new roof mounted HVAC equipment.
4. The existing glass store front system did not print on sheets A-0.4, A-1.0, A-1.0a, and A-1.2.
5. Please provide the Health Department activity number.
SHEET A-4.3
6. Please rework your accessible signage to comply with ICC ANSI 117.1, Section 703.
END OF REVIEW
04/20/2012 LOREN MAKUS ENGINEERING REVIEW Denied Site Plan must be approved.
04/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide the site utility drawing referenced on sheet P-2.0, showing the proposed gravity grease interceptor, and the size, route, and slope of the building sewer. Reference: Section 103.2.3, UPC 2006.
3. Provide the design for the water heater (P3) shelf referenced in detail 1/P-3.0. Reference: Section 314.5, UPC 2006.
4. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only (shown correctly in detail 6/P-4.0). Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
5. Appliances (e.g. chemical dispensers, ice tea makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
6. Each piece of equipment (e.g. carbonators) requiring backflow protection shall be independently protected. Reference: Sections 602.2 and 603.0, UPC 2006, as amended by the City of Tucson.
7. Provide separate indirect waste pipes for the ice maker and the ice storage bin. Reference: Section 801.2.3, UPC 2006.
8. Correct the sizes of the branch gas piping serving the fryers (21E) and the Chinese range (20Q); based on a developed pipe length of 150-feet, these pipes are too small. Reference: Section 1217.0, UPC 2006.
04/23/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the operation of the Type I hood and the hood exhaust fan complies with Section 507.2.1.1, IMC 2006.
2. Provide 18" clearance between the combustible-construction wall and the cook line shown in detail 3/A-1.2 (and in the detail on sheet M-3.0) or revise the construction of the wall as described in Section 507.9, IMC 2006.
3. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference: Section 606.1, IMC 2006.
04/23/2012 ROBERT SHERRY WATER REVIEW Denied Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly (according to a note on sheet P-1.0, this information is shown on a site utility drawing that was not submitted). Reference: Section 103.2.3, UPC 2006.
05/02/2012 CARL SCHULTZ FIRE REVIEW Denied PG A-1.0 Second exit door needs panic hardware IFC & IBC 1008.1.9
Hardware Schedule HW-2 does not call it out
05/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01914
2802 N Campbell
Panda Express

See Building Plans Examiner review, the drawings for the
Yogurt Space are to be taken out on a seperate permit.
Please remove these from this plan and resubmit for a seperate permit.
The plans for the Yogurt Space can be on the same set if a seperate taken out.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tucson
5/4/12
Ray.Majuta@tucsonaz.gov
05/07/2012 CAGUILA1 WWM REVIEW Needs Review
05/07/2012 CAGUILA1 ZONING REVIEW Needs Review