05/18/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 4: THE CALCULATIONS PROVIDED ON SHEET A6-C INDICATE ATTACHMENT OF THE WALL TOP TRACK TO PERPENDICULAR WALLS. INDICATE THIS CONNECTION ON A DETAIL ON THE PLANS, OR ON A PLAN NOTE.
2. PREVIOUS COMMENT 5: REFERENCE IS MADE TO SHEET A3.1C FOR EIFS IN KEYED NOTE 9 ON SHEET A1-C. THERE IS NO SHEET A3.1C INCLUDED IN THIS SET. PROVIDE.
3. PREVIOUS COMMENT 11: THE WALL ELEVATION INDICATED ON THE RIGHT SIDE OF THE BUILDING ON THE FLOOR PLAN ON SHEET A1-C HAS BEEN CHANGED TO 3/A2. THIS IS NOT CORRECT. REVISE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/23/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
05/23/2012 MARTIN BROWN FIRE REVIEW Approved
05/24/2012 STEVE SHIELDS ZONING REVIEW Approved
05/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved