Permit Number: T12CM01884
Parcel: 117021570

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM01884
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2012 GERRY KOZIOL WWM REVIEW Denied 1. DUPLEX UNIT #1 & #2
2. NEED PCRWRD REVIEW - PRIVATE SEWER CROSSING 207 W SPEEDWAY
3. NEED TO SHOW GREYWATER SYSTEM WITH DIVERSION VALVE TO SEWER
05/09/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-11-12
Activity: T12CM01884
Address: 1041 N 10th Av
Applicant: Earl Yousey

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

SITE PLAN:
1. Specify location of electric service feeders to the POA.
2. The water supply to all new multi-family residential buildings shall be individually metered for each dwelling unit, 301.4.1 as amended.

FLOOR PLAN:
3. The walls and soffit of the enclosed space under stairs shall be protected on the enclosed side with ½" gypsum board, R311.2.2.

SECTIONS - DETAILS:
4. Show two anchor bolts per plate on section details, R403.1.6.

PLUMBING PLAN:
5. Note: Segregation of first floor lavatories is optional in this situation.
6. Specify location of washing machine gray water discharge on first floor plumbing layout.
7. Specify the size of all plumbing vents, UPC 904.

ELECTRICAL PLAN:
8. Correct electrical riser diagram
o Feeders from one service panel may not pass through another service panel
o Specify size of conduit and feeder conductors to service panels
o Clarify grounding method (ICF?)
9. Provide smoke detectors in hallways leading to bedrooms on the second floor, R313.
10. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2012 GERARDO BONILLA OUT TO CUSTOMER Completed