Permit Number: T12CM01789
Parcel: 13416205D

Address:
7145 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01789
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide north arrows and scale on all full and partial floor plans.
SHEET TS
2. Accessibility Notes: Please revise all the accessibility notes, requirements and references to the 2006 IBC, Chapter 11 and ICC ANSI 117.1, 2003 Edition.
SHEET A2.2
3. As per the 2006 IBC, Section 1109.2.2, please provide 1 ambulatory toilet stall in the women's room.
4. In the men's room please change the width of the accessible urinal to 3'-0" as per ICC ANSI 117.1, Sections, 605.3, 305 and 305.7.
MORE GENERAL COMMENTS
5. All documents must have an Arizona registratnt seal and signature.
END OF REVIEW
04/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
3. Provide the scale for the mechanical floor plan. Reference: Section 106.3.1, IMC 2006.
4. The mechanical floor plan shows several HVAC diffusers located within twice the diameter of the large ceiling fans which is not recommended by the fan manufacturer. Revise the mechanical design so that the equipment is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2006.
5. Revise the mechanical design as required to avoid using the corridor in the area of the tanning rooms as a return air duct. Reference: Section 601.2, IMC 2006.
6. Show how the existing hydronic piping is to be relocated, the pipe sizes, and the required insulation for the pipes. Reference: Sections 106.3.1, 1204, and 1206, IMC 2006.
04/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
3. Either the 2006 Uniform Plumbing Code or the 2006 International Plumbing Code may be used for this activity. The plumbing General Notes on sheet P1.0 refer to the 2006 Uniform Plumbing Code but the "GOV.'N CODES" notes on sheet TS refer to the 2006 IPC. This review has been made using the 2006 IPC.
4. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
5. Provide the scale for the plumbing floor plan. Reference: Section 106.3.1, IPC 2006.
6. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp).
7. Provide plumbing plans for all of the new work, including water isometrics and waste and vent isometrics. Show the location of all required cleanouts on the waste and vent isometrics. Show how the new piping relates to the existing systems and show that the additional connections do not cause the existing piping to be overloaded. Reference: Sections 102.4 and 106.3.1, IPC 2006.
8. Correct detail F/P3.0; if the specified water heater is not supplied with integral heat traps, provide heat traps (not "heat trace") on the supply and discharge piping. Reference: Section 504.4, IECC 2006.
9. Provide tempered water for the lavatories using approved devices conforming to ASSE Standard 1070. The specified Kohler mixing valve conforms to ASSE Standard 1016 Reference: Section 416.5, IPC 2006.
10. Specify how the maximum mixed water temperature is to be limited for the showers. Reference: Sections 424.3, 424.4, and 607.1, IPC 2006.
11. Provide construction details to show that the site-built showers will comply with the requirements of Section 417, IPC 2006.
12. Provide water pressure and water pipe sizing calculations. Clarify the meaning of "CWFU". Reference: Section 604.1, IPC 2006.
13. The fixture connection sizes called out for the urinal flush valves on sheet P2.0 will result in water velocities greater than 8 FPS; the fixture schedule on sheet P1.0 shows the correct pipe size. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Section 604.4, IPC 2006.
14. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. the clothes washer). Reference: Section 604.9, IPC 2006.
15. The developed length of the hot water distribution system, from the water heater to the furthest outlet for hot water is in excess of 100-feet; provide a method of maintaining the water temperature (e.g. an automatic recirculating system) per Section 607.2, IPC 2006. Reference: Section 504.6, IECC 2006.
16. Provide a design for the modified natural gas system. Include each connected load (existing as well as new) and the developed pipe lengths from the meter to each load on the plans. Reference: Section 402.3, IFGC 2006.
04/27/2012 ROBERT SHERRY WATER REVIEW Denied Provide the size of water meter and of the reduced pressure backflow prevention assembly serving this building. Reference: Section 106.3.1, IPC 2006.
05/03/2012 CARL SCHULTZ FIRE REVIEW Denied Fire alarm system required TFC 907.2.1 please put ref. on plans.
All egress doors exiting to the outside required to have panic hardware and to be the only device on doors per city of modifications TFC 1028.6
05/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01789
7145 E 22ND ST
TI Fitness Center

1. Mechanical Sheets show 5 new exhuast fans, however not in Electrical Sheets.
2. Sheet E-2, the circuits marked P1 should be PB.
3. Sheet E-3, Interior Lighting Lighting Diagram, shows a
277 v circuit and several H circuits, change to correspond to correct circuits.
4. Sheet E-4 note regarding "provide boost x-frm for 230/240v equipment at each machine", please explain due to the existing voltage being 208v.
5. Sheet E-4 note " all existing mech equipment for this space from existing Panel AC or M" Panel P-2 shows 5 existing AC's ?
6. Provide a new total load for existing servoice MSB.


Ray t Majuta
Electrical Plan Review
PDSD, City of Tucson
5/9/2012
Ray.Majuta@tucsonaz.gov
05/17/2012 TERRY STEVENS ZONING REVIEW Approved
05/18/2012 GERRY KOZIOL WWM REVIEW Denied 1. CHUZE FITNESS
2.16 FU CREDIT GIVEN PER DEMO PLANS AND PERMIT #PT12S00559
3. NEEDS ADDRESS REVIEW
4. NEEDS CAPACITY REVIEW- KURT STEMM ON 3RD FLOOR