Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01755
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/23/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the plumbing code to be used for this activity. The notes on sheet T0.0 refer to both the 2006 UPC and the 2006 IPC as being applicable. This review has been made using the 2006 UPC. 2. Provide the minimum plumbing facilities (e.g. a drinking fountain) required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. See also, Section 1109.5.1, IBC 2006. 3. Show that the installation of the vacuum relief valve for the water heater complies with the manufacturer's listing requirements (i.e. no valves located between the vacuum relief valve and the water heater). Reference: Section 310.4, UPC 2006. 4. Provide a watertight pan of corrosion-resistant material under the water heater with a drain to an approved location. Reference: Section 508.4, UPC 2006. 5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. the clothes washer). Reference: Section 609.10, UPC 2006. 6. Provide upper terminal cleanouts on horizontal drainage pipes serving sinks (e.g. the mop sink). Reference: Section 707.4, UPC 2006. |
04/23/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/23/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 2. Revise the size of the proposed dryer exhaust duct to required minimum size of 4-inches in diameter. Reference: Sections 304.1 and 504.6, IMC 2006. |
05/01/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T0.0; PROJECT DATA: PROVIDE CONSTRUCTION TYPES (EXISTING AND NEW). 2. SHEET T0.0; PROJECT DATA: UNDER THE REQUIRED PLUMBING FIXTURES, DRINKING FOUNTAIN IS LISTED AS 0. VERIFY THAT WITH THE IBC TABLE 2902.1. 3. SHEET A1.1; RECEPTION DESK DETAIL 6 AND ELEVATIONS 3,4, AND 5: SECTION 904 OF THE ICC/ANSI A117.1-2003 REQUIRES AN ACCESSIBLE PORTION OF SALES OR SERVICE COUNTERS. MEET THOSE REQUIREMENT. 4. SHEET A1.1; OCCUPANCY TABULATION TABLE: THIS TABLE INDICATES 44 OCCUPANTS IN 1988.1 SF. WHAT IS THIS IN REFERENCE TO? A CALCULATION BELOW THE TABLE INDICATES 2041 SF WITH 20 OCCUPANTS. CLARIFY. 5. SHEET A12.0; DETAIL 2: GIVE A SIZE FOR THE STEEL STUD BRACE. CLARIFY THE BRACE CONNECTION ON THE LEFT. THE CONNECTION ON THE RIGHT INDICATES USING THE WEB OF A WOOD JOIST FOR LATERAL SUPPORT. VERIFY. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
05/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM01755 5977 E Grant Rd Electrical review comments from 4/11/2012 have not been addressed. Ray T Majuta Electrical Plan Reviw PDSD, City of Tucson 5/7/2012 Ray.Majuta@tucsonaz.gov |
05/10/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |