Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM01755
Parcel: 110162620

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T12CM01755
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
04/11/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/11/2012 MARTIN BROWN FIRE REVIEW Approved
04/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01755
5977 E Grant 115

1. 005 NEC 250.66 requires a # 2 equipment ground for the conductors from transformer to Panel A.
2. Sheet E-2 circuit HA-2 should be HA-3.
3. Provide a detail showing the support for transformer above tiolet rooms.
4. How will the transformer being installed above cieling comply with 2005 NEC 450.13.B ?
5. Tiolet rooms supplied with conditioned air how will Mechanical Plans Examiner requirements be met ?

Ray T Majuta
Elect Plan Review
PDSD,C of T
4/11/12
Ray.majuta@tucsonaz.gov
04/11/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T0.0; PROJECT DATA: PROVIDE CONSTRUCTION TYPES (EXISTING AND NEW).
2. SHEET T0.0; PROJECT DATA: UNDER THE REQUIRED PLUMBING FIXTURES, DRINKING FOUNTAIN IS LISTED AS 0. VERIFY THAT WITH THE IBC TABLE 2902.1.
3. SHEET A1.1; RECEPTION DESK DETAIL 6 AND ELEVATIONS 3,4, AND 5: SECTION 904 OF THE ICC/ANSI A117.1-2003 REQUIRES AN ACCESSIBLE PORTION OF SALES OR SERVICE COUNTERS. MEET THOSE REQUIREMENT.
4. SHEET A1.1; OCCUPANCY TABULATION TABLE: THIS TABLE INDICATES 44 OCCUPANTS IN 1988.1 SF. WHAT IS THIS IN REFERENCE TO? A CALCULATION BELOW THE TABLE INDICATES 2041 SF WITH 20 OCCUPANTS. CLARIFY.
5. SHEET A12.0; DETAIL 2: GIVE A SIZE FOR THE STEEL STUD BRACE. CLARIFY THE BRACE CONNECTION ON THE LEFT. THE CONNECTION ON THE RIGHT INDICATES USING THE WEB OF A WOOD JOIST FOR LATERAL SUPPORT. VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/11/2012 ENEWCOM1 ADA REVIEW Passed
04/11/2012 JASON GREEN ENGINEERING REVIEW Approved