Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T12CM01755
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/11/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/11/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM01755 5977 E Grant 115 1. 005 NEC 250.66 requires a # 2 equipment ground for the conductors from transformer to Panel A. 2. Sheet E-2 circuit HA-2 should be HA-3. 3. Provide a detail showing the support for transformer above tiolet rooms. 4. How will the transformer being installed above cieling comply with 2005 NEC 450.13.B ? 5. Tiolet rooms supplied with conditioned air how will Mechanical Plans Examiner requirements be met ? Ray T Majuta Elect Plan Review PDSD,C of T 4/11/12 Ray.majuta@tucsonaz.gov |
04/11/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T0.0; PROJECT DATA: PROVIDE CONSTRUCTION TYPES (EXISTING AND NEW). 2. SHEET T0.0; PROJECT DATA: UNDER THE REQUIRED PLUMBING FIXTURES, DRINKING FOUNTAIN IS LISTED AS 0. VERIFY THAT WITH THE IBC TABLE 2902.1. 3. SHEET A1.1; RECEPTION DESK DETAIL 6 AND ELEVATIONS 3,4, AND 5: SECTION 904 OF THE ICC/ANSI A117.1-2003 REQUIRES AN ACCESSIBLE PORTION OF SALES OR SERVICE COUNTERS. MEET THOSE REQUIREMENT. 4. SHEET A1.1; OCCUPANCY TABULATION TABLE: THIS TABLE INDICATES 44 OCCUPANTS IN 1988.1 SF. WHAT IS THIS IN REFERENCE TO? A CALCULATION BELOW THE TABLE INDICATES 2041 SF WITH 20 OCCUPANTS. CLARIFY. 5. SHEET A12.0; DETAIL 2: GIVE A SIZE FOR THE STEEL STUD BRACE. CLARIFY THE BRACE CONNECTION ON THE LEFT. THE CONNECTION ON THE RIGHT INDICATES USING THE WEB OF A WOOD JOIST FOR LATERAL SUPPORT. VERIFY. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
04/11/2012 | ENEWCOM1 | ADA | REVIEW | Passed | |
04/11/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved |