Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM01742
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/25/2012 MARTIN BROWN FIRE REVIEW Approved
05/29/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. After conferring with our staff structural engineer, Mr. Eric Newcomb, he is in agreement that structural calculations and details for suspension of the CENTRICITEE ceiling grid system is necessary. Please provide same.
2. Please provide structural calculations for detail 102 canteliever floor support with steel columns and concrete footings.
3. The special inspector certification was not attached with submittal. Please send again.
END OF REVIEW.
05/29/2012 ROBERT SHERRY WATER REVIEW Approved
05/30/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The flow rate for a water closet with a siphonic flushometer valve is approximately 25 GPM (1.6 GPF over 4 seconds); for a 1" Type L copper tube, this results in a velocity of 9.7 FPS and for a 1" PEX tube (Uponor) the velocity is 13.7 FPS. [Original comment: The branch piping sizes called out for the water closet flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.]
2. Verify the total for the gas inputs for the kitchen equipment; the revised total load appears to be 1685 CFH, not 1545 CFH. [Original comment: Verify and coordinate the natural gas inputs for the kitchen appliances with the food service drawings. Reference: Sections 103.2.3 and 1209.1, UPC 2006.]
3. Clarify the installation of KEQ#53: one unit is shown sheet p2.1 with no information and on sheet p4.1 the same unit is shown as having a trap and vent but no size information. On the kitchen equipment plans however, two KEQ#53 units are shown and the according to the manufacturer's data, the unit is a 12" x 84" trench drain with a 4" tailpiece. The second trench drain appears to be called out as a 2" hub drain on sheet p2.1. Revise the size of the waste and vent piping associated with these two trench drains. Reference: Sections 311.5 and 904.1, UPC 2006.
05/30/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/05/2012 GERRY KOZIOL WWM REVIEW Denied 1. TOBY KEITH'S
2. 4FU CREDIT PER PERMIT #PT04S01802 DATED
04/19/2004 PER WW/ES
3. NEED PCRWRD CAPACITY REVIEW - KURT STEMM 740-6607
4. NEED WW/IWC REVIEW OF GREASE INTERCEPTOR - TOM TOMCHAK 724-6200 3035 W EL CAMINO DEL CERRO

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2012 CPIERCE1 REJECT SHELF Completed
06/19/2012 CPIERCE1 APPROVAL SHELF Completed
06/19/2012 CINDY AGUILAR REJECT SHELF Completed