Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM01739
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Provide a description of how the existing mloads for the 2 200 amp disconnects were obtained, per 2005 NEC 220.87 Ray Majuta 4/10/12 |
| 04/11/2012 | LHANLY1 | ZONING | REVIEW | Passed | electrical branch circuits only for evse. no site changes |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |