Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM01558
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/13/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the required input for the natural gas to the new direct-fired heater; the shop drawing shows a maximum "Energy Production" of 1,139,000 BTUH (which is apparently the heater output) while the piping design calls for an input of 970 CFH (970,000 BTUH). Revise the pipe sizes as required. Reference: Section 1209.4.2, UPC 2006. 2. Show the location of the new gas pressure regulator and the discharge point for its vent. Reference: Sections 1209.7 and 1211.5.1, UPC 2006. |
| 04/13/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/13/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/13/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/20/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: O'Rielly Chevrolet - Paint Booth Addition T12CM01558 Building Plan (1st Review) TRANSMITTAL DATE: April 20, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until the development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/30/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-2; PLAN: SECTIONS B-B AND C-C ARE CUT ON THE PLAN LOOKING IN THE WRONG DIRECTION (PER THE SECTIONS). REVISE. 2. SHEET A-2; SECTION A-A: THIS SECTION IS CUT AT A LOCATION WHERE THE TUNNEL WOULD NOT BE SEEN. REVISE. 3. SHEET A-2; DETAILS J, K, L, AND M: PROVIDE THE ANCHOR SIZE, LENGTH, AND SPACING. 4. SHEET S1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 5. SHEET S1.1; ROOF FRAMING PLAN: REVISE THE ROOF DECK NOTE TO 22 GAUGE RATHER THAN 22#. 6. SHEET S1.1 (FOUNDATION PLAN); SHEET SD: PROVIDE A DETAIL AT THE TYPICAL SLAB TURNDOWN CONDITION. 7. SHEET S1.1; FOUNDATION PLAN: IS THE 4" BUILDING SLAB REINFORCED? PROVIDE A NOTE ON THE PLAN. 8. SHEET SD; SOIL NOTES: THIS SECTION INDICATES A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PROVIDE THAT REPORT FOR REVIEW. IF NO REPORT WAS USED, PROVIDE A PLAN NOTE INDICATING THE ASSUMED VALUE ALLOWED PER CODE FOR SOIL BEARING. 9. SHEET SD; STRUCTURAL STEEL NOTES: PROVIDE NOTES FOR THE STRUCTURAL STEEL CONNECTION BOLTS. 10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/01/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Jim Leitschuck DATE: May 1, 2012 1432 E. Van Buren FROM: Paul Machado Phoenix, Arizona 85006 Engineering Division Subject: O'rielly Chevrolet, Paint Booth Remodel Flood Plain Use Permit T12OT00594 (First Review) T14S, R14E, Section 13 RESUBMITTAL REQUIRED: Flood Plain Use Permit (FUP). The Flood Plain Use (FUP) permit cannot be approved as submitted. Please address the following review comments prior to the next submittal. Flood Plain Use Permit: 1. Please include a response letter to the comments along with the corrected copies of the FUP. 2. Provide proper documentation, on a company letter head, of the cost estimate of the improvements to the paint booth and the assessor's evaluation or an appraisal from a registered appraiser for the paint booth. Written costs estimates or appraisals on the back of the FUP application do not suffice. 3. The Site Plan, DP12-0046, cannot be approved prior to the approval of the FUP. If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson - Planning and Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4932 office (520) 879-8010 fax C:/6100 E BROADWAY BL 50% FUP Denial.doc |
| 05/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/23/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |