Permit Number: T12CM01550
Parcel: 137055330

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01550
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2012 TERRY STEVENS ZONING REVIEW Approved
04/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01550
5373 S Calle Santa Cruz #101

1. Provide a one line diagram for service showing which meter is to be used. Provide a location of this service. Show a new total amperage load including this new space along with any other loads on the main service.

Ray T Majuta
PDSD, C of Tucson
Elect Plan Review.
4/3/12
Ray.Majuta@tucsonaz.gov
04/03/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
04/03/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/03/2012 ERIC NEWCOMB ADA REVIEW Passed
04/03/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/04/2012 FRODRIG2 WWM REVIEW Needs Review
04/04/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/04/2012 ROBERT SHERRY WATER REVIEW Approved
04/04/2012 MARTIN BROWN FIRE REVIEW Approved