Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T12CM01523
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/12/2012 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | T12CM01523 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FLOOR PLANS: 1. Show the location of tempered glass within 18" of the floor and 24" of doorways, R308.4. CoT Amended. STRUCTURAL PLANS: 1. The braced wall panels are not consistent with the prescriptive options of the IRC, therefore provide an registered engineer's seal on the structural sheets of the plans. SECTIONS - DETAILS: 1. The ABE post base series shown on the post details, sheet #S1, has been discontinued. Revise the post foundation detail with the ABW44Z replacement device. PLUMBING PLANS: 1. Provide a water hammer arrester for quick-closing valves at the clothes washer, P2903.5. 2. Show the water service pipe (replace) size with sufficient capacity for controlling excessive flow rates for the building, P2903.6. A minimum 1" service pipe is required for delivering over 9.5 and less than 32 fixture units. MECHANICAL PLANS: 1. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1403. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU (1 ton cooling = 12,000 BTU). The 5 ton unit requires a minimum duct area of 360 square inches. Two 14" diameter ducts only provide 308 square inches. ELECTRICAL PLANS: 1. Show the relocated kitchen countertop receptacle outlets with a 2O AMP rating, E3603.2 and E3801.3. 2. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3801.11. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/17/2012 | FERNE RODRIGUEZ | REJECT SHELF | Completed |