Permit Number: T12CM01501
Parcel: 11619376B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01501
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/02/2012 ROBERT SHERRY WATER REVIEW Approved
04/02/2012 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
04/05/2012 STEVE SHIELDS ZONING REVIEW Approved
04/05/2012 MARTIN BROWN FIRE REVIEW Denied Drawings appear to not be drawn to scale. The scale of the bottom of sheets C1 and E3 do not match any of the options on my Engineering scale. Trying to establish existence of 4' wide travel lanes required by Fire Department. Please confirm.
04/13/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The letter for the structural engineer Lee S. Johnson analyzing the existing roof structure for the additional dead load of the PV panels does not address which roof. Please provide structural analysis for the existing two roof structures (Annex Roof and the Parking Garage Roof) that are to receive an additional load of PV panels.
2. On sheets S102B abd S112, please show the PV panel location and layout on the two different roof framing plans. Please have the structural engineer seal and sign both structural plan layouts.
END OF REVIEW
04/23/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01501
275 N commerce Park Loop
175.56 KW Photovoltaic System

1. How will the installation of the PV source comply with 2005 NEC 690.64(B)3., "The interconnection point shall be on the line side of all ground fault protection equipment." or the exception ?

Ray Majuta
Elect Plan Review
PDSD, C of Tuc
Ray.majuta@tucsonaz.gov
4/24/12