Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01501
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/02/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/02/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/05/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/05/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Drawings appear to not be drawn to scale. The scale of the bottom of sheets C1 and E3 do not match any of the options on my Engineering scale. Trying to establish existence of 4' wide travel lanes required by Fire Department. Please confirm. |
| 04/13/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. The letter for the structural engineer Lee S. Johnson analyzing the existing roof structure for the additional dead load of the PV panels does not address which roof. Please provide structural analysis for the existing two roof structures (Annex Roof and the Parking Garage Roof) that are to receive an additional load of PV panels. 2. On sheets S102B abd S112, please show the PV panel location and layout on the two different roof framing plans. Please have the structural engineer seal and sign both structural plan layouts. END OF REVIEW |
| 04/23/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM01501 275 N commerce Park Loop 175.56 KW Photovoltaic System 1. How will the installation of the PV source comply with 2005 NEC 690.64(B)3., "The interconnection point shall be on the line side of all ground fault protection equipment." or the exception ? Ray Majuta Elect Plan Review PDSD, C of Tuc Ray.majuta@tucsonaz.gov 4/24/12 |