Permit Number: T12CM01496
Parcel: 14041127A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM01496
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2012 MARTIN BROWN FIRE REVIEW Denied The density required of the water supply was not noted on the new plans. This is mandatory. Should be determined by a fire protection engineer. Many densities are available to protect storage, depending on method of storage, height of building and storage, aisle width, etc. The Fire Department needs this information so the plan review of the (deferred) sprinkler design insures the criteria established by the engineers has been satisfied. Also, the response letter indicates references to NFPA 231 and 231C have been removed. This did not happen.
05/16/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/17/2012 GERRY KOZIOL WWM REVIEW Denied 1. SHELL BUILDING - WAREHOUSE - DP12-033
2. NEED CIVIL UTILITY PLANS - NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - DOES NOT FRONT PUBLIC SEWER - MAY NEED TO BUILD PUBLIC SEWER - NEED PCRWRD PUBLIC SEWER REVIEW & APPROVAL - NEED PUBLIC SEWER CONSTRUCTION PERMIT - NEED HOLD HARMLESS LETTER
3. NO WASTEWATER PLUMBING STUB-OUTS - NO PLUMBING DRAWINGS ARE INCLUDED WITH THIS SHELL SUBMITTAL
4. NO TI'S UNTIL WASTEWATER SEWER CONNECTION FEES ARE PAID