Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM01496
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | The density required of the water supply was not noted on the new plans. This is mandatory. Should be determined by a fire protection engineer. Many densities are available to protect storage, depending on method of storage, height of building and storage, aisle width, etc. The Fire Department needs this information so the plan review of the (deferred) sprinkler design insures the criteria established by the engineers has been satisfied. Also, the response letter indicates references to NFPA 231 and 231C have been removed. This did not happen. |
| 05/16/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/17/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. SHELL BUILDING - WAREHOUSE - DP12-033 2. NEED CIVIL UTILITY PLANS - NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - DOES NOT FRONT PUBLIC SEWER - MAY NEED TO BUILD PUBLIC SEWER - NEED PCRWRD PUBLIC SEWER REVIEW & APPROVAL - NEED PUBLIC SEWER CONSTRUCTION PERMIT - NEED HOLD HARMLESS LETTER 3. NO WASTEWATER PLUMBING STUB-OUTS - NO PLUMBING DRAWINGS ARE INCLUDED WITH THIS SHELL SUBMITTAL 4. NO TI'S UNTIL WASTEWATER SEWER CONNECTION FEES ARE PAID |