Permit Number: T12CM01479
Parcel: 13419042A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM01479
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/16/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The mechanical exhaust hood data now approximates the kitchen equipment information but the air balance schedule and the exhaust fan schedule have not been modified as required. [Original comment: Clarify the relationship of the hoods and makeup air unit as shown in the mechanical drawings with the hoods and makeup air unit shown in the kitchen equipment shop drawings (i.e. which equipment will show up on the job site?) Reference: Section 106.3.1, IPC 2006.]
05/16/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/16/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/17/2012 GERRY KOZIOL WWM REVIEW Approved
05/17/2012 FRODRIG2 ZONING REVIEW Needs Review