Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM01479
Parcel: 13419042A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01479
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Freddy's Frozen Custard & Steakburgers
T12CM01479
Building Plan (1st Review)

TRANSMITTAL DATE: April 11, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/11/2012 JASON GREEN ENGINEERING REVIEW Approved Will stamp building plan approved once site review is complete.
04/12/2012 GBONILL1 FIRE REVIEW Approved
04/17/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide structural calculations for:
a. All exhaust hoods
b. All roof top mounted HVAC equipment
SHEET A1.1
2. Please provide accessible seating as required by the 2006 IBC, Section 1108.2.2.1 and show quantity and locations on the floor plan.
SHEET A3.1
3. At detail 5, provide all accessible requirements on the toilet partial plans which include dimensions, clearances (including door clearances), accessories and fixtures.
4. At detail 10, as per ICC A117.1, Section 306.3, clearance dimension from the bottom of the counter fascia is 2'-3" not 2'-2 3/4". Please correct dimension.
5. Please change all ADA references and titles to the 2006 IBC, Chapter 11 and ICC ANSI 117.1, 2003 Edition.
END OF REVIEW
04/18/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the relationship of the hoods and makeup air unit as shown in the mechanical drawings with the hoods and makeup air unit shown in the kitchen equipment shop drawings (i.e. which equipment will show up on the job site?) Reference: Section 106.3.1, IPC 2006.
04/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing waste floor plan and the waste and vent isometric (e.g. include the floor sink, P-4, located east of the mop sink). Reference: Section 106.3.1, IPC 2006.
2. Coordinate the Gas Meter Load data with the Gas Diagram and with the Plumbing Gas Floor Plan (e.g. the water heater is shown to have a 40 CFH input on the Gas Meter Load chart and 76 CFH input on the Gas Diagram; the total load on the gas meter is shown as 833 CFH on the floor plan but 797 CFH on the Gas Meter Load chart). Reference: Section 106.3.1, IPC 2006.
3. Correct the label for the condensate drain from AC-1. Reference: Section 106.3.1, IPC 2006.
04/18/2012 ROBERT SHERRY WATER REVIEW Approved
04/30/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01479
7120 E Broadway
TI Restaurant,Freddy's,Frozen Custard & Steakhouse

1. Provide 2006 IECC Budget Lighting Calculations and show compliance required to switching.
2. Sheet E1.1, Outdoor Lighting Calculation, the current
2012 Outdoor Lighting per Table 401.1 area E3 option 2 allows only 250,000 lumens per acre of full cut of lighting, and no unshielded lighting. Your calculation includes unshielded lighting ?
Also Fixtures "D" under the canopy are not counted if fully shielded, if unshielded they are to be counted, are they fully shielded ?
3. Sheet E2.1 shows circuit A-36 going to receptacles,however marked spare in panel schedule.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tucson
5/01/12
Ray.Majuta@tucsonaz.gov
05/10/2012 GERRY KOZIOL WWM REVIEW Denied 1. FREDDY'S FROZEN CUSTARD & STEAKBURGER - FORMERLY LONG JOHN SILVERS - DP12-0024 - OK TO ISSUE PER PCRWRD/CHAD AMATEAU 03/05/12
2. CONNECTIONG TO EXISTING ON SITE PRIVATE SEWER
3. 33FU CREDIT PER PERMIT #ZPA-8503 DATED 11/30/76, EXISTING PLANS y PHOTOS PER WW/ES DATED 02/24/12
4. NEED WW/IWC REVIEW & APPROVAL OF 1500 GALLON GREASE INTERCEPTOR 520-724-6200 F.T. "RUSTY" RICCABONI, JR