Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM01455
Parcel: 12810082B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01455
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
03/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/29/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/29/2012 ROBERT SHERRY WATER REVIEW Approved
03/29/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/29/2012 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
03/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/29/2012 JASON GREEN ENGINEERING REVIEW Approved
03/29/2012 MARTIN BROWN FIRE REVIEW Approved
03/29/2012 ERIC NEWCOMB ADA REVIEW Passed
03/29/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2012 GERARDO BONILLA APPROVAL SHELF Completed
04/06/2012 GERARDO BONILLA OUT TO CUSTOMER Completed