Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01412
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/27/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/28/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/28/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/28/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET g1.0; CODE ANALYSIS: THE OCCUPANCY TYPE IS LISTED AS A MIXED OCCUPANCY OF A-2, A-3, B, AND E. VERIFY THESE CLASSIFICATIONS APPLY TO THIS PROJECT PER THE 2006 IBC CHAPTER 3. 2. SHEET g1.0; OCCUPANCY LOAD: ALL OCCUPANCY LOADS ARE BASED ON B AND E OCCUPANCY CLASSIFICATIONS. WHERE DO THE A-2 AND A-3 CLASSIFICATIONS APPLY? VERIFY. 3. SHEET a4.0; DETAIL 4: PROVIDE THE METAL STUD BRACING SIZE AND CONNECTION TO THE WALL STUDS AND TO THE STRUCTURE ABOVE. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/28/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/28/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/28/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/28/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/28/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/30/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |