Permit Number: T12CM01406
Parcel: 122170660

Address:
1312 N JONES BL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM01406
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2012 GERRY KOZIOL WWM REVIEW Denied 1. NEED TO CLARIFY/IDENTIFY BUILDING ON SITE PLAN - FIRE DAMAGE REPAIR
2. RECOUNTED WASTEWATER PLUMBING FIXTURES - NEED 1ST FLOOR WASTEWATER MAPS & RECORDS CREDIT EVALUATION
04/11/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-11-12
Activity: T12CM01406
Address: 1308 N Jones Blvd
Applicant: Rob Prikosovits

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Specify all framing member sizes and spacing on framing plan including rafters, ledgers, and beams R802.1.

ELECTRICAL PLAN:
2. Use Table E3602.13 for sizing 15, 20 & 30 AMP branch circuit conductors.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2012 CPIERCE1 OUT TO CUSTOMER Completed