Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM01348
Parcel: 10604005F

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM01348
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2012 PAUL MACHADO ENGINEERING REVIEW Approved
03/23/2012 STEVE SHIELDS ZONING REVIEW Approved
03/26/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/26/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/26/2012 MARTIN BROWN FIRE REVIEW Approved