Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
07/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Existing MDP Panel still showing Transformer TLDP (225kva) on a 350 amp breaker.The plan now shows a new 112.5 kva transformer ,should be on a correct sized breaker and loads inserted in panel. Also an existing 75kva Transformer show be re-installed into this panel as it is remaining, loads to be intalled also.
2. The main circuit breaker for panel LC should be 150 amps due to the conductors being rated at 150 amps in table 310.16 in the 75degree C column.

Ray T Majuta
Elect Pln Review
PDSD, City of Tucson