Permit Number: T12CM01334
Parcel: 12801005H

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM01334
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review T12CM01334
5870 E Broadway #448
Total Wine

Revision needs to be submitted for review due to the following
1. New 112.5KW transformer
2.Service has been revised extensively
3.One panel deleted, two others ref from new transformer
4.Circuitry has been revised and redristributed

Ray T Majuta
Electrical Plan Review
PDSD City of Tucson
7/19/2012
Ray.Majuta@tucsonaz.gov
07/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The installation of a reduced pressure backflow prevention assembly will require a local drain for the backflow preventer, sized per Section 603.3.9, UPC 2006. A reduced pressure backflow prevention assembly is not required for this application; a different type of backflow preventer (e.g. a dual check valve) that does not require a drain can be utilized. [Original comment: A note in detail 3/A6.3 states that cold water is to be supplied to the refrigerated direct-draw dispenser; describe how this connection is to be accomplished. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. If required, specify the type of backflow prevention device is to be used. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.]
2. Provide a detail of the proposed connection; see Section 603.3.5, UPC 2006 for general instructions. [Original comment: Clarify the nature of the "growler drain" and provide justification for a continuous waste that appears to be over 6-feet in length. Reference: Sections 801.2 and 1001.2, UPC 2006.]
3. The use of an island vent is appropriate for this application but the design of the island vent shall comply with the detailed requirements shown in Section 909.0, UPC 2006. [Original comment: The vent pipe opening shall not be located below the weir of the trap serving the sink. Reference: section 904.5, UPC 2006.]

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2012 CPIERCE1 OUT TO CUSTOMER Completed