Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM01334
Parcel: 12801005H

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM01334
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A note in detail 3/A6.3 states that cold water is to be supplied to the refrigerated direct-draw dispenser; describe how this connection is to be accomplished. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. If required, specify the type of backflow prevention device is to be used. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
2. Clarify the nature of the "growler drain" and provide justification for a continuous waste that appears to be over 6-feet in length. Reference: Sections 801.2 and 1001.2, UPC 2006.
3. The vent pipe opening shall not be located below the weir of the trap serving the sink. Reference: section 904.5, UPC 2006.
07/19/2012 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2012 CPIERCE1 OUT TO CUSTOMER Completed