Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM01334
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/09/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A note in detail 3/A6.3 states that cold water is to be supplied to the refrigerated direct-draw dispenser; describe how this connection is to be accomplished. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. If required, specify the type of backflow prevention device is to be used. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 2. Clarify the nature of the "growler drain" and provide justification for a continuous waste that appears to be over 6-feet in length. Reference: Sections 801.2 and 1001.2, UPC 2006. 3. The vent pipe opening shall not be located below the weir of the trap serving the sink. Reference: section 904.5, UPC 2006. |
07/19/2012 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/19/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |