Permit Number: T12CM01334
Parcel: 12801005H

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM01334
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed; the submitted riser diagrams and enlarged plumbing plans do not show the new work indicated on sheet P1.1, revision 3. [Original comment: Provide sufficient details to evaluate the revision to the plumbing system, e.g. riser diagrams. Reference: Section 103.2.3, UPC 2006.]
06/29/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01334
5870 E Broadway Bl
Total Wine

1. Provide a revision sheet indicating the changes made and the sheets they apply to.
2. Sheet E 4.1, existing MDP does not indicate the new feeder to the new 75 KVA transformer feeding panels LA and LD.
3. Provide a location for new 75 kva transformer, if celing or wall supported provide a detail on the support.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tucson
6/29/2012
Ray.Majuta@tucsonaz.gov
07/06/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2012 GERARDO BONILLA OUT TO CUSTOMER Completed