Review Details: REVISION - - 1ST
Permit Number - T12CM01334
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/28/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed; the submitted riser diagrams and enlarged plumbing plans do not show the new work indicated on sheet P1.1, revision 3. [Original comment: Provide sufficient details to evaluate the revision to the plumbing system, e.g. riser diagrams. Reference: Section 103.2.3, UPC 2006.] |
| 06/29/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM01334 5870 E Broadway Bl Total Wine 1. Provide a revision sheet indicating the changes made and the sheets they apply to. 2. Sheet E 4.1, existing MDP does not indicate the new feeder to the new 75 KVA transformer feeding panels LA and LD. 3. Provide a location for new 75 kva transformer, if celing or wall supported provide a detail on the support. Ray T Majuta Electrical Plan Review PDSD, C of Tucson 6/29/2012 Ray.Majuta@tucsonaz.gov |
| 07/06/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2012 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |