Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01334
5870 E Broadway #144
Total Wine


The comments from previous electrical review (of 3/27/12)have not been reviewed.

Ray T Majuta
PDSD, C of Tuc
Electrial Plan Review
4/16/12
Ray.majuta@tucsonaz.gov
04/16/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. The Fixture Branch Connection Schedule on sheet P0.1 still indicates that the 3-compartment sink only has indirect waste connections; clarify that the wash and rinse compartments are to be directly-connected to sanitary waste. [Original comment: Provide an indirect connection for the sanitizing compartment of the 3-compartment sink, with a direct waste connection for the wash and rinse sections only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.]
04/16/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/18/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied RESUBMITTAL COMMENTS
Comment 1.
A deferred submittal correspondence to the building official is not required for the items listed on sheet CS1. However the prefabricated trellis appears to be a deferred submittal and needs to be documented to the building official as such.
Comment 2.
Sheets noted with City of Tucson non-compliant lettering sizes of 3/32" minimum height including both upper and lower case are: CS1, A1.3, SPEC 1 through and including SPEC 7, E0.1, E2.1, E2.3, E5.2, M1.1, MPE0.2, MPE0.3, MPE0.4 and P4.2.
Comment 6.
Neither water heater detail nor calculations are included in the structural documents with this resubmittal.
Comment 8.
Signage and detail location instructions that are not compliant with ICC A117.1 are still included on sheet A7. Please rework your signage details and specification to comply with ICC ANSI 117.1, Section 703.
END OF FIRST RESUBMITTAL REVIEW