Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM01334
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01334
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2012 MARTIN BROWN FIRE REVIEW Approved
03/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
2. Show how the exterior water piping (i.e. the hose bibb on the roof) is to be protected from freezing. Reference: Section 313.6, UPC 2006.
3. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
4. Show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatories (the temperature mixing valve in the plumbing fixture schedule is not shown on the plumbing plans). Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Provide an indirect connection for the sanitizing compartment of the 3-compartment sink, with a direct waste connection for the wash and rinse sections only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
6. Show the cleanouts for the fixtures in the wine classroom. Reference: Section 707.4, UPC 2006.
03/27/2012 ROBERT SHERRY WATER REVIEW Approved
03/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Replot sheets MPE0.1 - MPE0.4 for legibility. Reference: Section 106.1.1, IBC 2006.
2. The submitted Mechanical Compliance Certificate is for a location in Camp Verde, Arizona; use "Pima County < 4,000 Feet" as the location. The entry for Pima County can be found in the drop-down menu below "Codes" in the COMcheck program.
3. Revise the size of the condensate drains shown on sheet P1.1 per Section 307.2, IMC 2006 as amended by the City of Tucson.
4. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
5. Clarify the schedule for exhaust fan EF-1; the schedule calls for it to be interlocked with the operation of AC-6 but the air supplied to the rest rooms comes from RTU-2. Show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
6. The fan coil schedule shows that fan coils FCU-1a, FCU-1b, and FCU-2 are to use R-22 refrigerant. Explain how this is allowable under the EPA regulations that prohibit charging new appliances with virgin R-22.
03/28/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01334
5870 E Broadway #448
Total Wine TI


Electrical plans denied for following:
1. Sheet E1.1, all circuits must be identified by nunber and panel.
2. Sheet E2.1, the lighting circuits have an "L" designation only, there is no Panel L.
3. Sheet E3.1, all circuits for all equipment to be identified
by number and Panel.
4. Single Line Key Notes , Note # 8, the 1/0 GRD should be 2/0 per NEC 2005 250.66.
5.Sheet E4.2, Panels LA,LB,LC,LD and HA are new, circuits not yellow marked cannot be found in electrical plans.
6. See Mechanical Plans Examiner comments, the conditioned air supplied into the restrooms must be exhausted at the same time supplied.How will this be accomplished electrically.

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
3/27/12
Ray.majuta@tucsonaz.gov
03/30/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. IBC 106.3.4.2: Deferral of any submittal items requires prior approval by the building official. You may list your requested deferral items on company letterhead and email it directly to Ron.Boose@tucsonaz.gov.
2. There are several sheets thought this submittal that have lettering sizes below the COT standard of 3/32" (actual size) upper and lower case. Please revise all such lettering and resubmit.
3. Not a correction comment, but for approval of a special inspector or special inspection
agency it is necessary to provide a special inspection certificate with the top ½
sealed by the inspection agencies engineer of record. Special inspection certificates
may be submitted for approval by email or at our walk-thru counter prior to permit
issuance.
SHEET EP-1
4. Insure panic bars are installed on all exit doors as required by the 2006 IBC,
Section 1008.1.9.
SHEET A2.1
5. At Detail 4: The relocated curb ramp is part of an accessible parking marked crossing.
a. Please show extension of the painted markings.
b. Please provide a detectable warning strip as required by the 2006 IBC, Section
306.12.
c. Insure flared sides of the ramp are as per detail 8.
SHEET PO.1
6. At detail 6, please provide structural calculations for all wall mounted water
heaters.
SHEET A5
7. Provide vertical grab bars at the accessible water closet as peer ICC A117.1, Section
604.5.1.
SHEET A7
8. Provide location of door signage as per ICC A117.1, Section 703.11.
END OF REVIEW
04/04/2012 GERRY KOZIOL WWM REVIEW Approved