Permit Number: T12CM01307
Parcel: 10510252A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01307
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagrams for the water supply and for the waste and vent piping.
2. Show how the hub drains are to be installed (projection above the floor) and how the floor is to be made impervious.
3. All appliances that are to be directly connected to the water system shall either have internal air gaps, integral backflow devices, or be equipped with an approved backflow preventer.
4. Show how the temperature of the hot water at the lavatory is to be controlled
5. Provide a detail of the water heater installation showing the pipes, valves, expansion tank, etc.
04/05/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the size, routing, and termination of the condensate drain. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson
04/17/2012 FRODRIG2 WWM REVIEW Needs Review
04/17/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
04/17/2012 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review