Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01307
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/05/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagrams for the water supply and for the waste and vent piping. 2. Show how the hub drains are to be installed (projection above the floor) and how the floor is to be made impervious. 3. All appliances that are to be directly connected to the water system shall either have internal air gaps, integral backflow devices, or be equipped with an approved backflow preventer. 4. Show how the temperature of the hot water at the lavatory is to be controlled 5. Provide a detail of the water heater installation showing the pipes, valves, expansion tank, etc. |
04/05/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size, routing, and termination of the condensate drain. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson |
04/17/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
04/17/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
04/17/2012 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |