Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01307
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/22/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/23/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | NEED AN INTERLOCK OR TIME SWITCH TO CONTROL BATH EXHAUST FAN. IMC 403.2 ARE YOU SURE YOU WANT TO USE 25A AND 45A BREAKERS.....CODE COMPLIANT BUT FREQUENTLY REVISED IN FIELD DUE TO COST. |
| 03/23/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, routing, and termination of the condensate drain. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. 2. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. 3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust runs whenever air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006. |
| 03/23/2012 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | IBC 2902.2 REQUIRES SEPARATE TOILET FACILITIES FOR EACH SEX. PROVIDE DETAILS FOR SUSPENDED CEILINGS, SOFFITS, HARD LIDS ETC. ADD VERTICAL GRAB BAR @ WATER CLOSETS PER ANSI 117.1 |
| 03/23/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/23/2012 | LEERAY HANLY | ADA | REVIEW | Passed | |
| 03/23/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/23/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 04/05/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 04/05/2012 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |