Permit Number: T12CM01258
Parcel: 13818185A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM01258
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-27-12
Activity: T12CM01258 2nd review
Address: 216 E Inez St.
Applicant: JC Construction

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GREEN BUILDING ANALYSIS:
1. Credit 3.5 - Roof mounted turbine vents do not qualify as a whole house ventilation fan system.

STRUCTURAL / FRAMING PLAN:
2. Provide ceiling joists at the front porch tied to the bottom of both rafters or provide a beam at the ridge for sufficient structural integrity, R802.3, R802.3.1.
3. Justify ridge beam sizes at both carports for the proposed span and tributary load, R801.2.
4. Provide a header schedule consistent with Table 502.5(1) or specify size of steel lintels for all new openings in existing walls.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review