Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM01256
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 4 OF 8 (FRAMING ITEMS); STRUCTURAL CALCULATIONS (SHEET 7): THE CORNER COLUMNS INDICATED IN THE STRUCTURAL CALCULATIONS (3X3X.082) DOES NOT MATCH THE COLUMN SECTION CALLED OUT ON THE DRAWINGS (1 1/2 x 1 1/2 x 14 ga.). VERIFY. |