Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM01256
Parcel: 113100010

Address:
1545 E COPPER ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01256
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2012 MARTIN BROWN FIRE REVIEW Approved
03/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/23/2012 ROBERT SHERRY WATER REVIEW Approved
04/02/2012 JASON GREEN ENGINEERING REVIEW Approved Will stamp the building plan approved once the DP Package is approved.
04/04/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C3.5; DETAIL 2: COMPLETE THE REFERENCE FOR THE DETAIL OF THE NEW RETAINING WALL.
2. SHEET C3.6; ENTRY GATE PLAN: A SECTION CUT 1/C3.7 IS INDICATED AT THE ENTRY GATE. ON SHEET C3.7, 1 IS AN ENTRY GATE ELEVATION. CLARIFY.
3. SHEET C3.6; KEYNOTES: KEYNOTE 2 INDICATES A GUARD BOOTH PER MANUFACTURER SPECIFICATIONS. PROVIDE THOSE ALONG WITH CALCULATIONS AND DETAILS FOR THE CONNECTION OF THE BOOTH TO THE SLAB.
4. SHEET C3.7; SECTION 4: THE SECTION ON THE LEFT INDICATES (6) #4 VERTICALS IN THE UPPER PORTION OF THE COLUMN, WHILE SECTION Y GRAPHICALLY INDICATES (7) #4 VERTICALS. CLARIFY.
5. SHEET C3.8; GENERAL STRUCTURAL NOTES: THE FOUNDATION NOTES INDICATE A SOILS REPORT WAS USED FOR THE FOOTING DESIGN. PROVIDE THAT REPORT FOR REVIEW.
6. STRUCTURAL CALCULATIONS: CLARIFY WHICH CANTILEVERED RETAINING WALLS IN THE CALCULATIONS PERTAIN TO WHICH WALLS ON THE DRAWINGS.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM01545
Salpointe High School
North Campus Improvements

1. Sheet E1.1, provide a front elevation detail of how electrical equipment to be situated on wall behind building.
2. Provide a detail of pole base for new lights.
3. Provide information on 500KVA transformer T8, information such as a specification sheet.
4.Conerning the Gaurd House, is this a unit which will be provided with all electrical wiring, panel, equipment
complete ?
5.Appears all electrical equipment shown to be new on Sheet E3.0 will be outdoors, indicate NEMA rating.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tuc
4/12/12
Ray.majuta@tucsonaz.gov
04/13/2012 DAVID RIVERA ZONING REVIEW Denied Zoning cannot approve the plan until the DP is approved.