Permit Number: T12CM01253
Parcel: 136327830

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM01253
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM01253 R1
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

SITE PLAN:

1. Show compliance with the Pool Barrier requirement by including a 4' barrier between the addition openings (door/windows) and the pool, or show a continuous barrier around the pool, 2006 IRC Appendix G (Amendment).

SECTIONS - DETAILS:

1. Show wood framing members resting on concrete as pressure treated, R319.1 item 2. Clarify 11/S3.0.
2. Show the weep screed with a minimum clearance 4" above grade or 2" above paved areas, R703.6.2.1. Clarify 3/S3.0.

PLUMBING PLANS:

1. Provide a sanitary drainage connection from P-4 to the building drain consistent with chapter 30. A gray drain line may be added with a diverter valve and discharged consistent with appendix O.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/18/2012 GBONILL1 BUILDING-COMMERCIAL REVIEW Passed
07/26/2012 CAGUILA1 WWM REVIEW Needs Review