Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01172
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2012 | TERRY STEVENS | ZONING | REVIEW | Passed | |
| 03/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the design for the water heater support with the architect. 2. Provide for thermal expansion of the water heater per Section 607.3 IPC 2006. 3. Provide a vacuum relief for the water heater per Section 504.2, IPC 2006. 4. Clarify the termination point for the T&P relief pipe from the water heater. Reference: Section 504.6, IPC 2006. |
| 03/19/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/19/2012 | KBROUIL1 | FIRE | REVIEW | Approved | |
| 03/19/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/20/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/21/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 03/21/2012 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/21/2012 | FRODRIG2 | ADA | REVIEW | Needs Review | |
| 03/21/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |