Permit Number: T12CM01164
Parcel: 10408093B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM01164
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; Table 1106.3, IPC 2006 is used to determine the size horizontal rainwater piping and assumes full-flow conditions. The overflow opening in the collector box acts as a weir, not a pipe or channel, and requires specific calculations that are not covered by the tables in the code books. [Original comment: Provide calculations to show that the size of the overflow opening in the roof drain collector box has a drainage capacity equal to that of the scupper. Reference: Sections 1107.1 and 1107.3, IPC 2006.]
04/18/2012 TERRY STEVENS ZONING REVIEW Approved
04/26/2012 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/26/2012 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review