Review Details: COMMERCIAL - TI
Permit Number - T12CM01079
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 3: THE DIAGONAL WALL BRACING (WOOD STUDS) CONNECTION IS NOT INDICATED TO THE TOP OF THE PARTITION WALL OR TO THE ROOF STRUCTURE ABOVE. VERIFY. 2. PREVIOUS COMMENT 6: IBC SECTION 1017.1, EXCEPTION 4, INDICATES NO FIRE RESISTANCE RATING IS REQUIRED IF THE OCCUPANCY IS A GROUP B. THIS IS A GROUP M. VERIFY. 3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/23/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved |