Permit Number: T12CM01079
Parcel: 127030550

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM01079
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Chicago Store - 5646 E. Speedway Blvd.
T12CM01079
Building Plan (1st Review)

TRANSMITTAL DATE: March 14, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Show the future right-of-way (ROW) and future curb on the site plan.

3. Provide a street perimeter yard setback on the plan based on LUC 3.2.6.5.B

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
03/14/2012 LOREN MAKUS ENGINEERING REVIEW Approved
03/14/2012 ERIC NEWCOMB ADA REVIEW Passed
03/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE STRUCTURAL CALCULATIONS.
2. SHEET A1; FLOOR PLAN/REFLECTED CEILING PLAN: DETAIL 6/A1 IS CUT ON BOTH OF THESE PLANS, BUT IS INCORRECT. REVISE.
3. SHEET A1; DETAIL 5: PROVIDE THE WALL BRACING SIZE, SPACING, AND CONNECTION TO THE STRUCTURE ABOVE AND TO THE TOP OF THE PARTITION. INDICATE THE CONNECTION OF 2X4 WOD STUDS TO THE ROOF STRUCTURE.
4. SHEET A1; DETAIL 5: FOR THE ALTERNATE METHOD OF SUPPORT, PROVIDE THE CONNECTION OF THE WALL TO THE 2X4 WOOD STUDS AND THE CONNECTION OF THE 2X4 WOOD STUDS TO THE ROOF STRUCTURE.
5. SHEET A1; FLOOR PLAN: DETAILS 8/A2 AND 9/A2 ARE CUT ON THE PLAN, BUT ARE INCORRECT. REVISE.
6. SHEET A1; FLOOR PLAN: DOES THE CORRIDOR REQUIRE A FIRE RESISTANCE RATING PER THE IBC 1017.1? VERIFY.
7. SHEET A1; FLOOR PLAN: THE DRINKING FOUNTAIN AND MOP SINK ARE NOT INDICATED ON THE PLAN. PROVIDE.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/14/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/15/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/15/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/15/2012 ROBERT SHERRY WATER REVIEW Approved
03/15/2012 MARTIN BROWN FIRE REVIEW Approved
03/15/2012 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
03/15/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved