Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM01055
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/19/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/26/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/29/2012 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide Tucson outdoor lighting code compliance certificate. 2.Provide complete fault current analysis. 3.Provide complete panel schedule include circuit breaker and panel AIC ratiings. Plan review, Dan Santa Cruz |
| 04/05/2012 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/24/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |