Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM01054
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 03/13/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/13/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET TS1; OCCUPANT LOADS: REVISE THE OCCUPANT LOAD FOR RETAIL (M) OCCUPANCY. 2. SHEETS TS1 (AREA CALCULATION) AND C1.0 (SITE PLAN): REMOVE THE DESIGNATION "NEW". 3. SHEET C1.0; SITE PLAN KEYNOTES: IN NOTE 11, REVISE THE PRODUCT NAME TO SONOTUBE. 4. SHEET S1.0 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (PAGE 4): THE CALCULATION INDICATES A BEAM B2, BUT THE FRAMING PLAN DOES NOT SHOW THE BEAM. CLARIFY. 5. SHEET S1.0; DETAIL 2: REVISE THE PRODUCT NAME TO SONOTUBE. 6. SHEET S1.0: PROVIDE MATERIAL PROPERTIES ON THIS SHEET. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/13/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/14/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/14/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 03/15/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/15/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/22/2012 | FRODRIG2 | ENGINEERING | REVIEW | Needs Review |