Permit Number: T12CM01029
Parcel: 116182810

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM01029
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied The weight of the unit is 453 pounds. This weight divided over (3) rafters equates to an additional 151 pounds or 15.1 pounds per linear foot for each rafter. In addition to the 15 pounds per square foot of dead load and 20 pounds per square foot of minimum required live load, each rafter now must support more than 50 pounds per foot which is 28.2% more than allowable for a 2x6 spanning 10 feet. The unit must be located over an interior wall or the roof framing will need to be reinforced.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2012 CINDY AGUILAR APPROVAL SHELF Completed
03/22/2012 CINDY AGUILAR OUT TO CUSTOMER Completed