Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM00978
Parcel: 10408095C

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM00978
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
03/09/2012 MICHAEL ST. PAUL ZONING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2012 GERARDO BONILLA OUT TO CUSTOMER Completed