Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM00937
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 4075 N Highway DR T12CM00937 41,040 W Photovoltaic System The electrical plans have been denied for the following: 1.Sheet 5 , note 3, indicate on the one line where this label is to be located. 2. Sheet 5, indicate where note 9 is to be used on plan. 3. Sheet 5 , note 10, there is no combiner panel on this drawing ? 4. Sheet 5 , note 11, where and how is this ufer to be installed ? 5. The system must have a minimum # 8 Grounding electrode conductor originating at main service on through to inverters per 2005 NEC 690.47. 6. Sheet 6 , calculations use a 290W module using 8.86 amps ISC, the 285 w module on spec sheet indicates 8.86 amps for ISC, the ISC for the 290w module is 8.94 a ? 7. Sheet 6 indicate string information box using 6.47 a ISC , which appears to be from the 280w module ? Verify the correct specifications are to be used for the correct module. 8. Provide a location sheet for the inverters, combiner if used,inverters, new meter, AC(PV) disconnect and the 800 amp service. Ray T Majuta Elect Plan Review PDSD, C OF Tuc 3/24/12 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/27/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |