Permit Number: T12CM00933
Parcel: 115044910

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM00933
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; show the location of the subsoil drainage piping on the plans and provide sufficient information to show that the design of the subsoil drainage system complies with the requirements of Sections 111.1 and 1112.1, IPC 2006. [Original comment: Provide a design for the subsoil drainage system. Reference: Sections 1111.1 and 1112.1, IPC 2006.]
2. Comment not resolved; detail 3/P2.2 shows regulator #2 with a load of 5,000 CFH but the 2 PSI pipe feeding the regulator and the low pressure piping downstream from the regulator are noted as having a total load of 4,000 CFH. [Original comment: Clarify the total gas load on regulator #2; are there future loads being considered? Reference: Sections 106.3.1 and 402.2, IFGC 2006.]
04/17/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
04/18/2012 DAVID RIVERA ZONING REVIEW Approved
04/20/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved