Permit Number: T12CM00889
Parcel: 12218025B

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM00889
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2012 MARTIN BROWN FIRE REVIEW Approved
03/14/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET C1
1. The accessible route connection to the pedestrian way at Alvernon does not work. It connects to a sloping side of a curb ramp. Please redesign and resubmit.
a. The ramp detail reference at this ramp is incorrect, S/B 4/C2.
2. The pedestrian connection from the back of the building to the Lee Street right of way is non-compliant. Please provide an accessible connection from the North side of the building to the South side of the building and then to the Lee Street right of way.
3. Coordinate the building design shown on this sheet and the floor plan design shown on sheet A1. The rear accessible route and trash areas do not coincide.
SHEET C2
4. At detail 1, detectable warning strips are not required for accessible parking spaces and accessible aisles.
5. Detail 4 is for curb ramps in the right of way and should be designed as per COT DOT standard 207 series. This detail is an ICC A117.1 detail not used for public right of way accessibility.
SHEET A2
6. Provide attic ventilation as required by the 2006 IBC, section 1203.2.
SHEET S2
7. For the purpose of assessing additional plan review fees, please provide on an 8.5 x 11 sheet of letterhead stationary, a list of all the intended deferred submittals.
8. Please provide special inspection certifications for review and approval.
END OF REVIEW
03/16/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/16/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/16/2012 ROBERT SHERRY WATER REVIEW Approved
03/19/2012 LOREN MAKUS ENGINEERING REVIEW Approved
03/23/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved Plan ck. Dan Santa Cruz
04/03/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2012 CINDY AGUILAR OUT TO CUSTOMER Completed